How To Calculate Cable Sizes //free\\ Here

Where ( I_z ) = derated cable ampacity. Load: 5 kW heater, 230V AC, power factor = 1. ( I_b = 5000 / 230 = 21.74 A )

[ V_d = \frac\sqrt3 \times L \times I_b \times (R \cos\phi + X \sin\phi)1000 \text (for 3-phase) ] how to calculate cable sizes

Increase to 4 mm² (( R_ac ≈ 5.62 \text Ω/km )). Drop = ( 2 \times 40 \times 21.74 \times 5.62 / 1000 = 9.77V ) → 4.25% (still over). Increase to 6 mm² (( R_ac ≈ 3.71 )). Drop = ( 2 \times 40 \times 21.74 \times 3.71 / 1000 = 6.45V ) → 2.8% (acceptable). Where ( I_z ) = derated cable ampacity